Hybrid Solar Inverter MPPT/PWM Charge Controller 0.7KW 1.0KW

Hybrid Solar Inverter MPPT/PWM Charge Controller 0.7KW 1.0KW

-Pure sine wave output;

-Wide AC voltage input range, AVR output;

-Adopt traditional EI transformer , stable performance;

-LCD real-time display, concise and straightforward;

-Working modes: AC first or battery first optional, intelligent charging;

-RS232 communication port optional;

-Perfect protection system: Battery undervoltage, battery overvoltage, overload power, output short circuit, temperature;

Description

 

⌈ Application Area ⌋

Office and publice facilites, household system, network transmission equipment, manufacturing, control system, solar energy system, oil field, drilling field operation, etc.

Provide stable, reliable and safe solutions for families, islands, ships and other small photovoltaic power systems.

 

⌈ Technical Parameters ⌋

Specification
Model NB-T7011210212/24
Rated Power700W1000W
Peak Power(20ms)2100W3000W
Start Motor0.5HP1HP
Battery Voltage12VDC12/24VDC
Size(L*W*Hmm)410*143*210
Packing Size(L*W*Hmm)460*200*270
N.W.(kg)1113
G.W.(kg)(Carton Packing)1214
InputDC Input Voltage Range10.5-15VDC(Single battery voltage)
AC Input Voltage Range73VAC~138VAC /  145VAC~275VAC
AC Input Frequency Range45Hz~64Hz
Max AC charging current6A~15A (Depending on the model)
AC charging voltageLEAD battery:Charge Voltage :14V; Float Voltage:13.8V(Single battery voltage)
AC charging methodThree-stage (constant current, constant voltage, floating charge)
OutputEfficiency(Battery Mode)≥85%
Output Voltage(Battery Mode)110VAC±2%  / 220VAC±2%(Battery Mode)
Output Frequency(Battery Mode)50Hz±0.5 or 60Hz±0.5
Output Wave(Battery Mode)Pure Sine Wave
Efficiency(AC Mode)>99%
Output Voltage(AC Mode)110VAC±10%  / 220VAC±10%
Output Frequency(AC Mode)Tracking Automatically
Output waveform distortion(Battery Mode)≤3%(Linear load)
No load loss(Battery Mode)≤2.5%  rated power
No load loss(AC Mode) ≤2% rated power( charger does not work in AC mode)
No load loss(Energy saving Mode)≤10W
Battery TypeCustomize batteryCharge and discharge parameters of different types of batteries (such as lithium batteries, etc.)
can be customized according to user requirements
AlarmANormal working condition, buzzer has no alarm sound
BBuzzer sounds 4 times per second when battery failure, voltage abnormality, overload protection
CWhen the machine is turned on for the first time, the buzzer will prompt 5 when the machine is normal
Inside Solar controller
(Optional)
Charging ModePWM or MPPT
Charging current10A/20A/30A/40A/50A/60A
PV Input Voltage RangePWM: 15V-44V(12V system); 30V-44V(24V system)   /   MPPT: 15V-120V(12V system); 30V-120V(24V system)
Max PV Input Voltage(At 25℃)PWM: 50V(12V/24V system)  /  MPPT: 150V(12V/24V system)
PV Array Maximum Power12V system: 140W/280W/420W/560W/700W/840W; 24V system: 280W/560W/840W/1120W/1400W/1680W
Standby loss≤3W
Maximum conversion efficiency>95%
EnvironmentOperating temperature-10℃~40℃
Storage temperature-15℃~60℃
Noise≤55dB
Elevation2000m(More than derating)
Humidity0%~95% ,No condensation

 


⌈ System Application Diagram ⌋

 

⌈ Case ⌋

Get all the latest information on Events, Sales and Offers.

has been added to your cart:
Checkout